Plan Review Stops For Permit 20100019
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 10-12-2020 Cont ID  
Sent By cdorman Date 10-12-2020 Time 15:09 Rev Time 0.00
Received By cdorman Date 10-12-2020 Time 10:35 Sent To  
Notes
2020-10-12 10:35:46.0000010/12/20 RECEIVED REVISION FOR GENERATOR.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 10-01-2020 Cont ID  
Sent By cdorman Date 10-01-2020 Time 15:16 Rev Time 0.00
Received By cdorman Date 10-01-2020 Time 12:30 Sent To  
Notes
2020-10-01 15:16:19.00000RISER DIAGRAM: NEUTRAL CONDUCTOR MUST BE EXTENDED TO
 TRANSFER SWITCH (INSTALLED WITH UNGROUNDED CONDUCTORS)
 FOR BOTH SERVICE CONDUCTORS AND FEEDERS. SHOW
 NEUTRAL/GROUND BOND IN TRANSFER SWITCH. PROVIDE
 SPECIFICATION SHEET FOR TRANSFER SWITCH; MUST BE LISTED
 AS SERVICE-RATED.