Plan Review Stops For Permit 20090741
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 11-19-2020 Cont ID  
Sent By cdorman Date 11-19-2020 Time 16:30 Rev Time 0.00
Received By cdorman Date 11-17-2020 Time 13:53 Sent To  
Notes
2020-11-17 13:53:06.00000REVISED PLANS EMAILE IN FROM CHELSEA@SUNVENA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 09-30-2020 Cont ID  
Sent By cdorman Date 09-30-2020 Time 08:41 Rev Time 0.00
Received By cdorman Date 09-28-2020 Time 16:14 Sent To  
Notes
2020-09-30 08:41:04.00000SHEETS A-00 & S-01: ROOF LAYOUT DOES NOT COMPLY WITH
 FLORIDA FIRE PREVENTION CODE11.12.2.2.2. SHOW MINIMUM 3
 FOOT SEPARATION BETWEEN MODULES AND ROOF RIDGE.
 SHEET E-01: EQUIPMENT GROUNDING CONDUCTOR BETWEEN
 COMBINER PANEL AND PV DISCONNECT IS TOO SMALL FOR 80A
 OCPD. SHOW MINIMUM #8 CU.