-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 20090555
Plan Review Stops For Permit 20090555
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 09-25-2020 Cont ID  
Sent By cdorman Date 09-25-2020 Time 15:40 Rev Time 0.00
Received By cdorman Date 09-24-2020 Time 15:40 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 09-22-2020 Cont ID  
Sent By cdorman Date 09-22-2020 Time 13:16 Rev Time 0.00
Received By cdorman Date 09-22-2020 Time 12:23 Sent To  
Notes
2020-09-22 13:16:09.000001] PERMIT APPLICATION MUST SHOW STATE LICENSE NUMBER
 AND COUNTY REGISTRATION NUMBER.
 2] ON ONE-LINE DIAGRAM, SHOW QUANTITY OF MODULES ON
 EACH STRING
 3] ON ONE-LINE DIAGRAM, SHOW ACTUAL AC SYSTEM OUTPUT
 CURRENT ON COMBINER LABEL & PV DISCONNECT LABEL.
 CURRENT OUTPUT OF PROPOSED SYSTEM IS NOT 60 AMPS
 4] ON ONE-LINE DIAGRAM, ELIMINATE #10 GREEN EGC BETWEEN
 PV DISCONNECT AND SUPPLY SIDE TAP. PV DISCONNECT IS
 BONDED BY GROUNDED CIRCUIT CONDUCTOR, #8 CU MINIMUM.
  

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved