Plan Review Details - Permit 20080525
Plan Review Stops For Permit 20080525
Review Stop BLDREN REISSUANCE BUILDING PERMIT
Rev No 1 Status D Date 10-20-2020 Cont ID  
Sent By cdorman Date 10-20-2020 Time 15:40 Rev Time 0.00
Received By cdorman Date 10-19-2020 Time 14:44 Sent To  
Notes
2020-10-20 15:40:40.00000THIS REVISION WAS SUBMITTED AFTER COMPLETION OF
 PROJECT, AND INSPECTION WAS SCHEDULED FOR THE FOLLOWING
 DAY. SEE INSPECTION NOTES.
 PROVIDE AN AS-BUILT DRAWING ADDRESSING THE NOTED
 DEFICIENCIES.
  
 REVISED SHEET PV-3 (ONE LINE DIAGRAM) RECEIVED WITH THE
 FOLLOWING DEFICIENCIES:
 1] TEN-MODULE STRING REQUIRES 15A OVERCURRENT
 PROTECTION PRIOR TO 70A PV DISCONNECT.
 2] SHOW CONDUCTOR SIZE BETWEEN "OLD" SYSTEM AND PV
 DISCONNECT.
 3] CONDUCTORS ON UTILITY SIDE OF PV DISCONNECT MUST
 INCLUDE A MINIMUM #8 CU GROUNDED CONDUCTOR BONDED TO PV
 DISCONNECT ENCLOSURE. REVISE CONDUCTOR & CONDUIT
 SCHEDULE ACCORDINGLY.
 4] VERIFY MICROINVERTER MODEL AND MAXIMUM OUTPUT
 CURRENT (PER UNIT) IS ACCURATE ON BOTH OLD AND NEW
 SYSTEM.
  
2020-10-19 14:44:32.00000REVISED PLANS REQUESTED BY PLANS EXAMINER SUBMITTED.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 11-04-2020 Cont ID  
Sent By cdorman Date 11-04-2020 Time 08:23 Rev Time 0.00
Received By cdorman Date 11-03-2020 Time 13:46 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 08-25-2020 Cont ID HC01455-03
Sent By cdorman Date 08-25-2020 Time 14:04 Rev Time 0.00
Received By cdorman Date 08-21-2020 Time 13:37 Sent To  
Notes
***NONE***