-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 20070164
Plan Review Stops For Permit 20070164
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status C Date 07-08-2020 Cont ID  
Sent By cdorman Date 07-08-2020 Time 15:10 Rev Time  
Received By cdorman Date   Time   Sent To  
Notes
2020-07-08 15:09:52.00000CONDITIONAL APPROVAL REQUIRES COMPLIANCE WITH NOTE ON
 RISER DIAGRAM: USE 60A FUSES IN PV DISCONNECT. 37
 INVERTERS @ 1.21 - 1.26A, PLUS 25% CONTINUOUS LOAD
 FACTOR REQUIRES 60A OCPD.