Plan Review Details - Permit 20060271
Plan Review Stops For Permit 20060271
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cdorman Date 08-04-2020 Time 15:47 Sent To  
Notes
2020-08-04 16:03:08.00000REVISION #3, SIX PAGES RECEIVED. THE FOLLOWING
 CORRECTIONS ARE REQUIRED.
 1] SHEET PV-2: INSERT NOTE ON DRAWING INDICATING
 COMPLIANCE WITH FLORIDA FIRE PREVENTION CODE
 11.12.2.2.2, AND CLEARLY SHOWING MINIMUM THREE FOOT
 SEPARATION BETWEEN MODULES & ROOF RIDGE.
 2] SHEET PV-4: 30A PV DISCONNECT IS TOO SMALL FOR
 COMBINED INVERTER OUTPUT.
  

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 06-30-2020 Cont ID  
Sent By cdorman Date 06-30-2020 Time 08:35 Rev Time 0.00
Received By cdorman Date 06-30-2020 Time 08:35 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 06-11-2020 Cont ID  
Sent By cdorman Date 06-11-2020 Time 08:46 Rev Time 0.00
Received By cdorman Date 06-10-2020 Time 15:52 Sent To  
Notes
2020-06-11 08:46:33.00000SHEET PV-4.0, CONDUIT/CONDUCTOR SCHEDULE ITEMS #5, 6, &
 7: EQUIPMENT GROUNDING CONDUCTOR MUST BE MINIMUM #6 AWG
 COPPER (OVERCURRENT PROTECTION GREATER THAN 100A AND
 NOT EXCEEDING 200A).