-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 20050465
Plan Review Stops For Permit 20050465
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status C Date   Cont ID  
Sent By   Date 05-28-2020 Time   Rev Time 0.00
Received By nsulliva Date 05-22-2020 Time 15:21 Sent To  
Notes
2020-05-28 08:21:37.00000I HAVE REVIEWED THE SUBMITTED PLANS AND DOCUMENTS FOR
 THE FIRE SUPPRESSION SYSTEM TO BE INSTALLED IN THE LP
 GAS CYLINDER PAINT BOOTH AT KOSAN CRISPLANT AND HAVE
 THE FOLLOWING COMPLAINTS:
  
 1. SHOW AUTOMATIC SHUT-OFF FOR CONVEYOR UPON ACTIVATION
 OF SUPPRESSION SYSTEM.
 2. SHOW AUTOMATIC SHUT-OFF FOR EXHAUST FAN UPON
 ACTIVATION OF SUPPRESSION SYSTEM.
 3. SUBMIT PLANS FOR SYSTEM STAMPED BY ENGINEER
 QUALIFIED IN THIS SUBJECT.
  
 PLEASE LET ME KNOW IF YOU HAVE ANY QUESTIONS OR NEED
 ANYTHING FURTHER.
  
 I AM APPROVING WORK TO START BASED ON KNOWLEDGE OF
 CONTRACTOR’S QUALITY OF WORK AND PAST PERFORMANCE WITH
 EXPECTATION OF CORRECT PLANS BEING SUBMITTED PRIOR TO
 FINAL INSPECTION AND TESTING.
  
 PAUL ANDERSON, JR.
 CAPTAIN, FIRE PREVENTION
 HIGHLANDS COUNTY FIRE RESCUE
 6850 W GEORGE BLVD.  SEBRING, FL 33875
 (O) 863-385-1112  (C) 863-381-6796  (F)
 863-402-7400
 ONLINE HTTP://WWW.HIGHLANDSFL.GOV
  
  
  
  
2020-05-22 15:21:48.00000THREE (3) COPIES SENT TO COUNTY FIRE FOR REVIEW CARRIER
 ERIC LONGSHORE.

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved