-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 20040492
Plan Review Stops For Permit 20040492
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 05-15-2020 Cont ID  
Sent By cdorman Date 05-15-2020 Time 13:27 Rev Time 0.00
Received By cdorman Date 05-14-2020 Time 14:35 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 04-27-2020 Cont ID  
Sent By cdorman Date 04-27-2020 Time 15:13 Rev Time 0.00
Received By cdorman Date 04-27-2020 Time 12:50 Sent To  
Notes
2020-04-27 15:10:48.00000RISER DIAGRAM IS INCONSISTENT, NEEDS CLARIFICATION.
 HEADING INDICATES 15 MODULES (TYPICALLY ONE STRING);
 DIAGRAM INDICATES TWO STRINGS OF 16 MODULES EACH;
 COMBINER PANEL INCLUDES O/C PROTECTION FOR TWO STRINGS.
 COMBINER PANEL OPERATING CURRENT AND PV DISCONNECT
 OPERATING CURRENT SHOULD MATCH.

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved