Plan Review Details - Permit 20030428
Plan Review Stops For Permit 20030428
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 03-27-2020 Cont ID  
Sent By cdorman Date 03-27-2020 Time 15:15 Rev Time 0.00
Received By cdorman Date 03-27-2020 Time 12:43 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status C Date 03-18-2020 Cont ID HC04350
Sent By cdorman Date 03-18-2020 Time 11:18 Rev Time 0.00
Received By cdorman Date 03-17-2020 Time 13:25 Sent To  
Notes
2020-03-18 11:18:08.000001] ROOF LAYOUT DOES NOT PROVIDE ADEQUATE DETAIL TO
 VERIFY SEPARATION BETWEEN MODULES & ROOF RIDGE.
 MAINTAIN MINIMUM THREE FOOT SEPARATION FROM RIDGE PER
 FL FIRE PREVENTION CODE 11.12.2.2.2.2
 2] RISER DIAGRAM PAGE HEADING INDICATES A TOTAL OF 24
 MODULES; INDIVIDUAL STRING DRAWING INDICATES 14 MODULES
 PER STRING (TOTAL OF 28). RISER DIAGRAM IS APPROVED AS
 DRAWN PROVIDED THAT NO MORE THAN 12 MODULES PER STRING
 ARE INSTALLED.

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved