Plan Review Details - Permit 19100637
Plan Review Stops For Permit 19100637
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 09-02-2020 Cont ID  
Sent By cshackel Date 09-02-2020 Time 09:41 Rev Time 0.00
Received By cshackel Date 08-28-2020 Time 15:57 Sent To  
Notes
2020-08-28 15:59:35.00000THREE (3) SET OF REVISED PLANS SUBMITTED FOR REVIEW,
 TWO (2) COPIES SENT TO COUNTY FIRE FOR REVIEW CARRIER
 ERIC LONGSHORE.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 02-07-2020 Cont ID  
Sent By elongsho Date 02-07-2020 Time 12:49 Rev Time 0.00
Received By elongsho Date 01-29-2020 Time 11:25 Sent To  
Notes
2020-01-29 11:26:52.000001/29/20 THREE SET OF REVISED PLANS SUBMITTED FOR
 REVIEW.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status R Date 12-11-2019 Cont ID  
Sent By elongsho Date 12-11-2019 Time 17:28 Rev Time 0.00
Received By elongsho Date 10-28-2019 Time 12:32 Sent To  
Notes
2019-12-11 17:28:40.00000PLANS RETURNED WITH FIRE AND BUILDING COMMENTS.

Review Stop ETRANSPCON TRANSPORTATION CONCURRENCY
Rev No 1 Status   Date 05-15-2020 Cont ID  
Sent By mcarner Date 05-15-2020 Time 10:28 Rev Time 0.00
Received By mcarner Date 05-15-2020 Time 10:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date 02-07-2020 Cont ID  
Sent By elongsho Date 02-07-2020 Time 12:49 Rev Time  
Received By elongsho Date   Time   Sent To  
Notes
2020-01-29 11:29:03.000001/29/20 TWO (2) SET OF REVISED PLANS SUBMITTED FOR
 REVIEW-SENT TO COUNTY FIRE CARRIER ERIC LONGSHORE.
  
2019-11-21 10:51:38.00000 
  
  
 HIGHLANDS COUNTY FIRE RESCUE
 FIRE PREVENTION BUREAU 6850 WEST GEORGE BOULEVARD
 SEBRING, FLORIDA 33870
 863-385-1112
  
  
  
  
  
  
  
  
  
  
  
  
 MEMORANDUM
 TO: ERIC LONGSHORE, BUILDING OFFICIAL
  
 FROM: JAMES E. BRANCA, SR., BATTALION CHIEF, FIRE
 MARSHAL
  
 DATE: NOVEMBER 21, 2019
  
 RE: NEW FIRE/EMS HEADQUARTERS BUILDING, PERMIT 19100637
  
  
 I HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, 6TH EDITION, AND
 NEED THE FOLLOWING ISSUES RESOLVED:
  
 1. THE FIRE SPRINKLERS IN THE WAREHOUSE ARE CALCULATED
 AS LIGHT HAZARD AND SHOULD BE AT A MINIMUM
 ORDINARY HAZARD.
 2. THERE SHOULD BE CO DETECTORS AT ALL OPENINGS TO THE
 WAREHOUSE.
 3. NOT SURE ABOUT THE PURPOSE OF THE SMOKE/FIRE DAMPER
 IN THE MEZZANINE. PLEASE EXPLAIN.
 4. FIRE ALARM SYSTEM SHOULD HAVE TAMPER SWITCHES AT THE
 FIRE SPRINKLER BACKFLOW VALVES.
 5. A BI-DIRECTIONAL EXIT LIGHT IS NEEDED AT THE
 INTERSECTION OF CORRIDOR 130 AND 115, IN FRONT OF
 ROOM 118.
 6. PAGE A301 SHOWS A DIRECTIONAL EXIT LIGHT FROM ROOM
 106 TO CORRIDOR 102 IN THE WRONG DIRECTION.
 7. THE GENERATOR CONTROLLERS NEED TO BE MONITORED BY
 THE FIRE ALARM FOR THE FOLLOWING CONDITIONS:
 • GENERATOR RUNNING.
 • GENERATOR FAULT.
 • GENERATOR SWITCH IN NONAUTOMATIC POSITION.
 8. SEPARATE PERMITS ARE NEEDED FOR:
 • AUTOMATIC FIRE SPRINKLER SYSTEM (BOTH ABOVE GROUND
 AND UNDERGROUND).
 • FIRE ALARM SYSTEM.
 • ACCESS CONTROL SYSTEM.
  
 PLEASE HAVE THE APPLICANT ADDRESS THESE ISSUES.
  
 IF THERE ARE ANY QUESTIONS I CAN BE REACHED AT
 863-385-1112
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 P A G E | 1
 MEMORANDUM
 TO: ERIC LONGSHORE, BUILDING OFFICIAL
 FROM: JAMES E. BRANCA, SR., BATTALION CHIEF, FIRE
 MARSHAL
 DATE: NOVEMBER 21, 2019
 RE: NEW FIRE/EMS HEADQUARTERS BUILDING, PERMIT 19100637
 I HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, 6TH EDITION, AND NEED THE
 FOLLOWING ISSUES RESOLVED:
 1. THE FIRE SPRINKLERS IN THE WAREHOUSE ARE CALCULATED
 AS LIGHT HAZARD AND SHOULD BE AT A MINIMUM ORDINARY
 HAZARD.
 2. THERE SHOULD BE CO DETECTORS AT ALL OPENINGS TO THE
 WAREHOUSE.
 3. NOT SURE ABOUT THE PURPOSE OF THE SMOKE/FIRE DAMPER
 IN THE MEZZANINE. PLEASE EXPLAIN.
 4. FIRE ALARM SYSTEM SHOULD HAVE TAMPER SWITCHES AT THE
 FIRE SPRINKLER BACKFLOW VALVES.
 5. A BI-DIRECTIONAL EXIT LIGHT IS NEEDED AT THE
 INTERSECTION OF CORRIDOR 130 AND 115, IN FRONT OF ROOM
 118.
 6. PAGE A301 SHOWS A DIRECTIONAL EXIT LIGHT FROM ROOM
 106 TO CORRIDOR 102 IN THE WRONG DIRECTION.
 7. THE GENERATOR CONTROLLERS NEED TO BE MONITORED BY
 THE FIRE ALARM FOR THE FOLLOWING CONDITIONS:
 • GENERATOR RUNNING.
 • GENERATOR FAULT.
 • GENERATOR SWITCH IN NONAUTOMATIC POSITION.
 8. SEPARATE PERMITS ARE NEEDED FOR:
 • AUTOMATIC FIRE SPRINKLER SYSTEM (BOTH ABOVE GROUND
 AND UNDERGROUND).
 • FIRE ALARM SYSTEM.
 • ACCESS CONTROL SYSTEM.
 HIGHLANDS COUNTY FIRE RESCUE
 FIRE PREVENTION BUREAU 6850 WEST GEORGE BOULEVARD
 SEBRING, FLORIDA 33870
 863-385-1112
  
  
  
  
  
  
  
  
  
  
  
  
 MEMORANDUM
 TO: ERIC LONGSHORE, BUILDING OFFICIAL
  
 FROM: JAMES E. BRANCA, SR., BATTALION CHIEF, FIRE
 MARSHAL
  
 DATE: NOVEMBER 21, 2019
  
 RE: NEW FIRE/EMS HEADQUARTERS BUILDING, PERMIT 19100637
  
  
 I HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, 6TH EDITION, AND
 NEED THE FOLLOWING ISSUES RESOLVED:
  
 1. THE FIRE SPRINKLERS IN THE WAREHOUSE ARE CALCULATED
 AS LIGHT HAZARD AND SHOULD BE AT A MINIMUM
 ORDINARY HAZARD.
 2. THERE SHOULD BE CO DETECTORS AT ALL OPENINGS TO THE
 WAREHOUSE.
 3. NOT SURE ABOUT THE PURPOSE OF THE SMOKE/FIRE DAMPER
 IN THE MEZZANINE. PLEASE EXPLAIN.
 4. FIRE ALARM SYSTEM SHOULD HAVE TAMPER SWITCHES AT THE
 FIRE SPRINKLER BACKFLOW VALVES.
 5. A BI-DIRECTIONAL EXIT LIGHT IS NEEDED AT THE
 INTERSECTION OF CORRIDOR 130 AND 115, IN FRONT OF
 ROOM 118.
 6. PAGE A301 SHOWS A DIRECTIONAL EXIT LIGHT FROM ROOM
 106 TO CORRIDOR 102 IN THE WRONG DIRECTION.
 7. THE GENERATOR CONTROLLERS NEED TO BE MONITORED BY
 THE FIRE ALARM FOR THE FOLLOWING CONDITIONS:
 • GENERATOR RUNNING.
 • GENERATOR FAULT.
 • GENERATOR SWITCH IN NONAUTOMATIC POSITION.
 8. SEPARATE PERMITS ARE NEEDED FOR:
 • AUTOMATIC FIRE SPRINKLER SYSTEM (BOTH ABOVE GROUND
 AND UNDERGROUND).
 • FIRE ALARM SYSTEM.
 • ACCESS CONTROL SYSTEM.
  
 PLEASE HAVE THE APPLICANT ADDRESS THESE ISSUES.
  