Plan Review Stops For Permit 19090509
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status C Date 10-03-2019 Cont ID HC04105-01
Sent By cdorman Date 10-03-2019 Time 16:36 Rev Time 0.00
Received By cdorman Date 09-25-2019 Time 11:50 Sent To  
Notes
2019-10-04 09:33:52.00000LEFT MESSAGE, READY FOR PICK UP 10/04/2019
2019-10-03 16:35:55.00000FUSES IN PV AC DISCONNECT MUST BE LIMITED TO 90 AMP FOR
 USE WITH #4 THWN COPPER.