Plan Review Details - Permit 19070057
Plan Review Stops For Permit 19070057
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 02-26-2020 Cont ID  
Sent By cdorman Date 02-26-2020 Time 15:37 Rev Time 0.00
Received By cdorman Date 02-26-2020 Time 13:24 Sent To  
Notes
2020-02-26 13:25:39.000002/26/20 RECEIVED TWO (20 SET OF REVISED PLANS FOR
 REVIEW.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status   Date 07-03-2019 Cont ID  
Sent By cdorman Date 07-03-2019 Time 12:26 Rev Time 0.00
Received By cdorman Date 07-02-2019 Time 15:43 Sent To  
Notes
2019-07-03 12:22:48.00000PER 690.9 (A), THE BACKFED PV INPUT BREAKER IN THE
 SERVICE PANEL ALSO PROVIDES OVERCURRENT PROTECTION FOR
 CONDUCTORS AND CURRENT-LIMITED EQUIPMENT (IN THIS CASE
 THE INVERTER AND THE CONDUCTORS FROM THE SERVICE PANEL
 TO THE INVERTER). CHANGE THIS CIRCUIT BREAKER TO A 30
 AMP, BASED ON USE OF A 5KW INVERTER.