Plan Review Details - Permit 19070055
Plan Review Stops For Permit 19070055
Review Stop BLDREN REISSUANCE BUILDING PERMIT
Rev No 1 Status A Date 07-19-2019 Cont ID  
Sent By cdorman Date 07-19-2019 Time 16:24 Rev Time 0.00
Received By cdorman Date 07-19-2019 Time 13:04 Sent To  
Notes
2019-07-22 12:44:56.00000REVISION APPROVED 07/22/19
2019-07-19 16:23:57.00000REVISION PLAN REVIEW FEE APPLIES. PER CONTRACTOR
 CERTIFICATION, NO CHANGE IN VALUATION FROM ORIGINAL
 APPLICATION.
2019-07-19 13:04:39.00000BROUGHT IN REVISIONS 07/19/19

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status C Date 07-03-2019 Cont ID  
Sent By cdorman Date 07-03-2019 Time 12:39 Rev Time 0.00
Received By cdorman Date 07-02-2019 Time 15:39 Sent To  
Notes
2019-07-03 12:39:23.00000PER 690.9 (A), THE BACKFED PV INPUT BREAKER IN THE
 SERVICE PANEL ALSO PROVIDES OVERCURRENT PROTECTION FOR
 CONDUCTORS AND CURRENT-LIMITED EQUIPMENT (IN THIS CASE
 THE INVERTER AND THE CONDUCTORS FROM THE SERVICE PANEL
 TO THE INVERTER). CHANGE THIS CIRCUIT BREAKER TO A 40
 AMP, BASED ON USE OF A 7.6KW INVERTER.