Plan Review Details - Permit 19060552
Plan Review Stops For Permit 19060552
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 07-09-2019 Cont ID  
Sent By cdorman Date 07-09-2019 Time 15:36 Rev Time 0.00
Received By cdorman Date   Time   Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 06-28-2019 Cont ID HC03288
Sent By cdorman Date 06-28-2019 Time 16:28 Rev Time 0.00
Received By cdorman Date 06-28-2019 Time 13:55 Sent To  
Notes
2019-06-28 16:28:08.00000SHEET E-1: CONDUCTORS BETWEEN ENPHASE COMBINER BOX AND
 THE FUSED DISCONNNECT ARE SHOWN AS #10 CU THWN.
 AMPACITY OF THESE CONDUCTORS IS NOT SUFFICIENT FOR 125%
 OF TOTAL PV OUTPUT OF 38 AMPS. SHOW A MINIMUM CONDUCTOR
 SIZE OF #8 THWN CU.