Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date   Cont ID  
Sent By   Date 06-27-2019 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2019-06-27 09:51:03.00000KERRY BARNETT FIRE SAFETY CONSULTING, LLC
 43951 CR 54E, KATHLEEN, FL 33849
  
 FIRE SAFETY INSPECTOR & PLANS EXAMINER CELL (813)
 778-4981
 KERRY BARNETT E-MAIL:
 KBARNETT@FIRESAFETYCONS.COM
 ________________________________________
 PLAN REVIEW #: 19-059 19060426 CONTRACTOR: RANDY
 WRIGHT CONSTRUCTION
 PROJECT: AAB METAL OFFICE BUILDING TELEPHONE:
 863-443-1220
 LOCATION: AVON PARK ENGINEER: COOL & COBB ENGINEERING
 ADDRESS OF JOB: US 27 N CONTACT: MASON COBB
 PAGES: 7 TELEPHONE: 863-657-2323
  
 JUNE 26, 2019
  
 I HAVE RECEIVED AND REVIEWED THE PLANS FOR A DUPLEX
 MIXED (BUSINESS/STORAGE) COMMERCIAL BUILDING WITH ONE
 SIDE BUILT OUT AND OTHER SIDE SHELL ONLY FOR COMPLIANCE
 WITH THE FLORIDA FIRE PREVENTION CODE AND ANY OTHER
 APPLICABLE NFPA STANDARD AND/OR CODE. AT THIS TIME,
 PLANS ARE ALLOWED TO MOVE FORWARD WITH COMMENTS NOTED
 BELOW. WITH ACCEPTANCE OF PERMIT, CONTRACTOR AGREES TO
 COMPLY WITH THE COMMENTS. SHOULD THE CONTRACTOR OR
 ENGINEER HAVE ANY QUESTIONS WITH THE COMMENTS, THESE
 SHALL BE RESOLVED PRIOR TO PERMITTING.
  
 1. THE FUTURE SPACE SHALL BE BUILT OUT UNDER A SEPARATE
 PERMIT AND PLANS.
 2. THE EMERGENCY LIGHT ABOVE THE DOOR FROM BUSINESS TO
 STORAGE, SHALL BE CHANGED OUT TO A COMBINATION
 EXIT/EMERGENCY LIGHT.
 3. FIRE SEPARATION WALL SHALL BE LABELED/MARKED IN
 ACCORDANCE WITH CHAPTER 8 OF NFPA 101.
 4. ENSURE THE 2 LAYERS OF RATED DRYWALL, THE JOINTS ARE
 STAGGERED IN ACCORDANCE WITH U419 LISTING. ALSO ENSURE
 THE APPROPRIATE ATTACHMENT METHOD IS USED IN ACCORDANCE
 WITH THE LISTING.
 5. ENSURE FIRE SEPARATION WALL IS FIRE CAULKED AT ROOF
 DECK AND DOWN THE SIDE WALL. RATED DRYWALL SHALL EXTEND
 ALL THE WAY TO THE ROOF DECK AND SIDE WALL, CUTTING
 AWAY ANY EXISTING INSULATION IF NECESSARY.
 6. THE DOOR FRAME SHALL BE A RATED 90-MINUTE STEEL DOOR
 FRAME, WRAP AROUND TYPE. ENSURE THE RATED DRYWALL
 EXTENDS BEHIND THE FRAME BY MINIMUM OF ½ INCH.
 7. MINIMUM 6” ADDRESS ABOVE EACH ENTRANCE DOOR. IF
 BUILDING HAS ITS OWN ADDRESS WITH SUITE A AND SUITE B,
 THEN SUITE AND SUITE A AND SUITE B SHALL BE ABOVE THE
 DOOR AND THE BUILDING ITSELF WILL HAVE THE MAIN
 NUMERICAL ADDRESS.
 8. THERE WERE NO PENETRATION UL LISTINGS FOR ELECTRICAL
 AND MECHANICAL. ANY PENETRATION OF THE FIRE RATED
 ASSEMBLY SHALL BE COMPLETED BY AN APPROVED LISTING.
 THIS LISTING SHALL BE PROVIDED AT THE INSPECTION FOR
 THE PENETRATIONS.
  
  
 INSPECTION REQUIRED:
  
 1. SCREW INSPECTION FOR EACH LAYER
 2. PENETRATION INSPECTION
 3. FINAL FIRE ASSEMBLY INSPECTION, INCLUDE INSPECTION
 OF FIRE DOORS.
 4. BUILDING FIRE FINAL
  
 KERRY BARNETT
 ___________________________________
 KERRY BARNETT, FIRE SAFETY INSPECTOR & PLANS EXAMINER
  