-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 19060088
Plan Review Stops For Permit 19060088
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 08-29-2019 Cont ID  
Sent By cshackel Date 08-29-2019 Time 08:18 Rev Time 0.00
Received By cshackel Date 06-05-2019 Time 08:36 Sent To  
Notes
2019-07-16 08:51:13.00000THESE PLANS HAVE BEEN SUBMITTED AS PRELIMINARY
 DEVELOPMENT ORDER AND ARE NOT CONSTRUCTION PLANS AS
 PLANS ARE NOT COMPLETE. PLANS ARE BEING RETURNED TO
 APPLICANT WITH PARTIAL APPROVAL FROM FIRE MARSHAL FOR
 SITE WORK.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status A Date   Cont ID  
Sent By   Date 08-27-2019 Time   Rev Time 0.00
Received By   Date 07-20-2019 Time   Sent To  
Notes
2019-08-27 12:44:43.00000MEMORANDUM
 TO: ERIC LONGSHORE, BUILDING OFFICIAL
 FROM: JAMES E. BRANCA, SR., BATTALION CHIEF, FIRE
 MARSHAL
 DATE: AUGUST 27, 2019
 RE: FLORIDA HOSPITAL HEARTLAND, 24 BED BUILDOUT AND
 CARDIAC CENTER, 4200 SUN N LAKES BLVD. SEBRING, FLORIDA
 33872
 I HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, SIXTH EDITION. PLEASE
 HAVE THE APPLICANT ADDRESS THE FOLLOWING COMMENTS:
 1. ON PAGES G110 AND G111 THE ONE HOUR FIRE BARRIER
 SEPARATING SMOKE COMPARTMENT SC-1K AND SC-1L DOES NOT
 COMPLETELY MAKE A FIRE BARRIER. INSTEAD IT ADJOINS A
 ONE HOUR SMOKE WALL.
 2. ON PAGE M112 THERE IS A FIRE DAMPER IN THE SMOKE
 WALL SEPARATING ROOM 1843 CLEAN HOLD FROM THE SHELL. IF
 IT IS FOUND THAT THIS SHOULD ALSO BE A FIRE WALL IN
 ACCORDANCE WITH THE PREVIOUS COMMENT, THEN IT SHOULD BE
 A COMBINATION FIRE/SMOKE DAMPER.
 I AM RETURNING THESE PLANS TO YOUR OFFICE WITH APPROVAL
 TO MOVE FORWARD WITH THE PERMIT PROCESS CONTINGENT ON
 RESOLUTION OF THE ABOVE COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status R Date 07-11-2019 Cont ID  
Sent By hlopez Date 07-11-2019 Time 13:09 Rev Time 0.00
Received By hlopez Date 06-05-2019 Time 08:36 Sent To  
Notes
2019-07-11 13:09:36.00000MEMORANDUM
  
 TO: ERIC LONGSHORE, BUILDING OFFICIAL
  
 FROM: JAMES E. BRANCA, SR., BATTALION CHIEF, FIRE
 MARSHAL
  
 DATE: JULY 11, 2019
  
 RE: FLORIDA HOSPITAL HEARTLAND, 24 BED BUILDOUT – EARLY
 SITE & STRUCTURE PACKAGE,
 4200 SUN N LAKES BLVD. SEBRING, FLORIDA 33872
  
  
  
 I HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, SIXTH EDITION.
 ALL REFERENCES MADE TO NFPA 1 OR NFPA 101 WITHIN THIS
 DOCUMENT ARE THE FLORIDA SPECIFIC VERSION.
 PLEASE HAVE THE APPLICANT ADDRESS THE FOLLOWING
 COMMENTS:
  
 1. ON PAGES G110 AND G111 THE ONE HOUR FIRE BARRIER
 SEPARATING SMOKE COMPARTMENT SC-1K AND SC-1L
 DOES NOT COMPLETELY MAKE A FIRE BARRIER. INSTEAD IT
 ADJOINS A ONE HOUR SMOKE WALL. FURTHERMORE,
 MECHANICAL ROOM 1051 AND ELECTRICAL ROOM 1047 SHOULD BE
 ONE HOUR FIRE RATED. (NFPA 101, SECTIONS
 18.3.2.1 AND 8.7)
 2. THE PROPOSED OVERHANG DOES NOT SPECIFY THE VERTICAL
 CLEARANCE. THIS CLEARANCE MUST HAVE AT A
 MINIMUM 13’ 6” FOR EMERGENCY VEHICLE ACCESS. (NFPA 1,
 CHAPTER 18)
 3. THE PLANS ARE MISSING THE FOLLOWING ELEMENTS:
 • FIRE ALARM
 • FIRE SPRINKLER
 • ELECTRICAL
 • HVAC/MECHANICAL
  
 IT IS NOTED THAT THESE PLANS ARE AN “EARLY SITE &
 STRUCTURE PACKAGE” WITH THE FACILITY WANTING
 TO BEGIN SITE WORK WHILE WAITING FOR THE FULL PLANS TO
 BE SUBMITTED AND APPROVED. ON FEBRUARY
 22, 2019, I REVIEWED THE PRELIMINARY, AND FINAL SITE
 PLANS FOR A DEVELOPMENT ORDER APPLICATION.
 THOSE PLANS DID NOT GENERATE ANY FIRE CODE COMMENTS.
 THE DEMOLITION AND PHASING PLANS APPEAR TO BE
 COMPLIANT WITH THE FIRE CODES. THAT SAID MY OFFICE DOES
 NOT OBJECT TO COMMENCING PREVIOUSLY
 APPROVED SITE WORK, WORK NOTED ON PAGES AD100 THROUGH
 AD232, AND THE SLAB.
  
 I AM RETURNING THESE PLANS TO YOUR OFFICE WITHOUT FULL
 APPROVAL.
  

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved