-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 19060081
Plan Review Stops For Permit 19060081
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 06-07-2019 Cont ID  
Sent By cdorman Date 06-07-2019 Time   Rev Time 0.00
Received By cdorman Date 06-07-2019 Time   Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 06-06-2019 Cont ID  
Sent By cdorman Date 06-06-2019 Time 16:17 Rev Time 0.00
Received By cdorman Date 06-04-2019 Time 13:26 Sent To  
Notes
2019-06-06 16:17:19.00000REFERENCE 705.12 (D)(2)(3)(B): 125% OF INVERTER OUTPUT
 PLUS MAIN BREAKER RATING EXCEED 120% OF BUSSBAR RATING
 PER SUBMITTED DRAWINGS.
 CALC: (6000 X 1.25) / 240 = 31.25 AMPS.
 31.25 + 150 MAIN = 181.25 AMPS
 150A BUSS RATING X 1.2 = 180 AMPS.
 USE 200 AMP BUSS RATING WITH 150A MAIN OR USE
 SUPPLY-SIDE TAP FOR PV INPUT.

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved