Plan Review Details - Permit 19050663
Plan Review Stops For Permit 19050663
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 08-12-2019 Cont ID  
Sent By cdorman Date 08-12-2019 Time 14:56 Rev Time 0.00
Received By cdorman Date 08-12-2019 Time 14:55 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status C Date 08-08-2019 Cont ID  
Sent By cdorman Date 08-08-2019 Time 16:29 Rev Time 0.00
Received By cdorman Date 08-08-2019 Time 08:55 Sent To  
Notes
2019-08-08 16:27:54.00000PER INSPECTION NOTES 6/24/19, UNGROUNDED CONDUCTORS
 BETWEEN THE POWER COLLECTION PANEL AND THE SUPPLY-SIDE
 CONNECTION SHOULD BE #3 COPPER, NOT #4 COPPER. PV
 OUTPUT CIRCUITS ARE CONSIDERED CONTINUOUS LOADS.
 (7600 + 11400) X 1.25 /240 = 98.96 AMPS.
 REQUEST CONTRACTOR TO PROVIDE FILE ATTACHMENT LETTER OR
 REVISED DRAWING SHOWING CORRECT SIZE CONDUCTORS.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status R Date 07-12-2019 Cont ID  
Sent By cdorman Date 07-12-2019 Time 16:07 Rev Time 0.00
Received By cdorman Date   Time   Sent To  
Notes
2019-07-12 16:07:09.000001] PROVIDE LETTER CERTIFYING NEW JOB VALUATION
 2] PROVIDE REVISED ROOF PLAN
 3] PROVIDE DRAWING OR INFORMATION SHOWING TOTAL NUMBER
 OF MODULES IN EACH STRING (CAN BE INCORPORATED INTO
 ROOF PLAN)
 4] PROVIDE SPECIFICATION SHEET FOR 11.4KW INVERTER

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 05-31-2019 Cont ID  
Sent By cdorman Date 05-31-2019 Time 16:15 Rev Time 0.00
Received By cdorman Date 05-31-2019 Time 14:11 Sent To  
Notes
2019-07-12 09:51:45.00000BROUGHT IN REVISED DRAWING 07/12/2019