2019-07-15 15:16:01.00000BROUGHT IN REVISED PLANS AND REBUTTALS 07/15/2019
2019-06-27 09:36:14.00000 
 MEMO: PERMIT #19050501
 FLORIDA CANCER SPECIALISTS
  
 I HAVE REVIEWED THESE PLANS AND HAVE THE FOLLOWING
 COMMENTS THAT NEED TO BE ADDRESSED.
  
 1. THE EXIT SIGN AT DOOR #133 NEEDS TO BE RELOCATED TO
 THE CORRIDOR SIDE OF THE DOOR.
 2. DOOR #184 NEEDS TO SWING IN THE DIRECTION OF TRAVEL.
 (OR REMOVE EXIT SIGNAGE)
 3. EXIT SIGN NEEDS TO BE ADDED TO DOOR #111.
 4. ALTHOUGH FE PLACEMENT MEETS CODE REQUIREMENT I
 SUGGEST TO ADD FE IN HALL 182 IN EXIT DISCHARGE AREA.
 5. FOOTER TS-1 IS ONLY DESIGNATED ON PLAN AT THE ENTRY
 AREA. ASSUMPTION IS MADE THAT THIS FOOTER IS CONTINUOUS
 FOR ENTIRE PERIMETER. CLARIFICATION CAN BE MADE BY
 ADDING DESIGNATION TO PLANS TO MATCH WF2.0 MARKINGS.
 6. FOOTER TS-1 IS LISTED AS 1’ WIDE AND 2’ DEEP. IS
 THIS CORRECT OR WAS INTENTION FOR IT TO BE 2’ WIDE AND
 1’ DEEP AS DRAWN IN DETAILS?
  
 PLANS AND APPLICATION WILL BE RETURNED TO SUBMITTER TO
 ADDRESS THESE COMMENTS ALONG WITH THE FIRE REVIEW
 COMMENTS (SEE ATTACHED) AND RESUBMITTAL. ALONG WITH
 RESUBMITTAL IT IS REQUESTED THAT A PDF OF REVISED PLANS
 BE SENT TO ‘PLANS@HCBCC.ORG’ FOR IMPORT INTO OUR
 SYSTEM.
  
  
  
  
 SINCERELY,
  
 ERIC R. LONGSHORE
 BUILDING OFFICIAL
  
2019-05-23 11:43:05.00000THREE (3) SET OF PLANS SUBMITTED FOR REVIEW ONLY, TWO
 SET FORWARDED TO COUNTY FIRE FOR REVIEW CARRIER ERIC
 LONGSHORE.

Review Stop ENGINEER SITE & DRAINAGE FDO
Rev No 1 Status A Date 07-31-2019 Cont ID  
Sent By cshackel Date 07-31-2019 Time 13:12 Rev Time 0.00
Received By cshackel Date 07-31-2019 Time 13:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date 07-18-2019 Cont ID HC04188
Sent By cshackel Date 07-18-2019 Time   Rev Time 0.00
Received By cshackel Date 05-23-2019 Time 11:42 Sent To  
Notes
2019-06-19 08:36:20.000004. IS THERE AN ISOLATION VALVE IN THE WATER SYSTEM TO
 THE NORTH OF THE “POINT OF SERVICE” FOR THE FIRE LINE?
 THE PLAN CLEARLY REFLECTS A VALVE TO THE SOUTH.
 5. THE FIRE ALARM SYSTEM SHOULD SUPERVISE THE GENERATOR
 FOR THE FOLLOWING:
 NFPA 101
 9.1.3.2 NEW GENERATOR CONTROLLERS SHALL BE MONITORED BY
 THE FIRE ALARM SYSTEM, WHERE PROVIDED, OR AT AN
 ATTENDED LOCATION, FOR THE FOLLOWING CONDITIONS:
 (1) GENERATOR RUNNING
 (2) GENERATOR FAULT
 (3) GENERATOR SWITCH IN NONAUTOMATIC POSITION
 I AM RETURNING THESE PLANS TO YOUR OFFICE WITHOUT FIRE
 CODE APPROVAL UNTIL ALL COMMENTS HAVE BEEN RESOLVED.
 PLEASE HAVE THE APPLICANT CONTACT ME WITH ANY
 QUESTIONS.
2019-06-19 08:36:12.00000FIRE REVIEW: MEMORANDUM
 TO: ERIC LONGSHORE, BUILDING OFFICIAL
 FROM: JAMES E. BRANCA, SR., BATTALION CHIEF, FIRE
 MARSHAL
 DATE: JUNE 18, 2019
 RE: FLORIDA CANCER SPECIALIST PERMIT #19050501
 I HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE 6TH EDITION, AND HAVE THE
 FOLLOWING COMMENTS THAT NEED ADDRESSED:
 1. THE OVERHANG AT THE FRONT ENTRANCE WILL NEED A
 MINIMUM OVERHEAD CLEARANCE OF 12’ FOR COUNTY AMBULANCE
 ACCESS.
 NFPA 1
 18.2.3.4.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13’
 6”.
 18.2.3.4.1.2.1 VERTICAL CLEARANCE SHALL BE PERMITTED TO
 BE REDUCED, PROVIDED SUCH REDUCTION DOES NOT IMPAIR
 ACCESS BY FIRE APPARATUS, AND APPROVED SIGNS ARE
 INSTALLED AND MAINTAINED INDICATING THE ESTABLISHED
 VERTICAL CLEARANCE WHEN APPROVED.
 2. HVAC SMOKE DETECTORS NEED TO BE LOCATED AS FOLLOWS:
 NFPA 90A
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS
 IN AIR SUPPLY SYSTEMS HAVING A CAPACITY GREATER THAN
 2000 FT3/MIN.
 3. HVAC SMOKE DETECTORS NEED TO BE SUPERVISED BY THE
 FIRE ALARM SYSTEM.
 NFPA 90A
 6.4.4.2 IN ADDITION TO THE REQUIREMENTS OF 6.4.3, WHERE
 AN APPROVED FIRE ALARM SYSTEM IS INSTALLED IN A
 BUILDING, THE SMOKE DETECTORS REQUIRED BY THE
 PROVISIONS OF SECTION 6.4 SHALL BE CONNECTED TO THE
 FIRE ALARM SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS
 OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE.