-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 18100020
Plan Review Stops For Permit 18100020
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 10-29-2018 Cont ID HC04035
Sent By elongsho Date 10-29-2018 Time 15:51 Rev Time 0.00
Received By elongsho Date 10-01-2018 Time 13:39 Sent To  
Notes
2018-10-17 13:31:45.00000**BROUGHT BACK THREE SETS OF REVISED PLANS WITH LIFE
 SAFETY ETC... 10/17/2018**
2018-10-03 12:51:09.00000MADE PRELIMINARY REVIEW AND SITE VISIT WITH FIRE
 MARSHAL. PLANS WILL NEED ADDITIONS.
 1. COVER SHEET STATING USE AND OCCUPANCY DESIGNATION,
 OCCUPANT LOAD AND TYPE OF CONSTRUCTION.
 2. SCALED FLOOR PLAN CLEARLY DEPICTING WALLS TO BE
 DEMOED AND WALLS TO BE ADDED.
 3. USE OF EACH ROOM DESIGNATED ON PLANS.
 4. A LIFE SAFETY PLAN SHOWING EXIT TRAVEL DISTANCES,
 EMERGENCY/EXIT SIGNAGE AND FIRE EXTINGUISHER PLACEMENT.
 5. PLUMBING DETAIL OF ADDED SHOWER.
 6. PLANS MUST NOTE THAT ALL PATIENT CARE AREAS MUST
 HAVE BRANCH CIRCUIT WIRING PER NEC 517.13.
  
 FIRE MARSHAL HAS QUESTIONED IF FIRE RATED CORRIDORS MAY
 BE NEEDED. FURTHER DETERMINATION OF THIS MAY REQUIRE
 ADDITION OF THIS TO PLANS ALSO.
2018-10-01 13:49:36.00000THREE (3) COPIES SUBMITTED FOR REVIEW, TWO COPIES
 FORWARD TO COUNTY FIRE FOR REVIEW.

Review Stop ETRANSPCON TRANSPORTATION CONCURRENCY
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date 10-29-2018 Cont ID HC04035
Sent By elongsho Date 10-29-2018 Time 15:51 Rev Time 0.00
Received By elongsho Date 10-01-2018 Time 13:46 Sent To  
Notes
***NONE***