Plan Review Stops For Permit 18070555
Review Stop BLDREN REISSUANCE BUILDING PERMIT
Rev No 1 Status A Date 11-18-2020 Cont ID  
Sent By cshackel Date 11-18-2020 Time 13:27 Rev Time 0.00
Received By cshackel Date 11-18-2020 Time 13:27 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 03-04-2019 Cont ID  
Sent By cshackel Date 09-22-2018 Time   Rev Time 0.00
Received By cshackel Date 07-23-2018 Time 15:26 Sent To  
Notes
2019-01-03 11:12:12.00000RECEIVED REVISED ELECTRIC PLANS FROM CONTRACTOR
 01/03/2019
2018-09-25 08:17:55.00000PLAN REVIEW NOTES: ROYAL OAKS TRIPLEX PERMIT # 18070555
  
 I HAVE REVIEWED THE PLANS FOR THIS PROJECT AND THE
 FOLLOWING ITEMS NEED TO BE ADDRESSED FOR RESUBMITTAL OF
 PLANS;
  
 1: A SECONDARY MEANS OF EGRESS WILL HAVE TO BE ADDED TO
 THE “DEN” IN UNIT 2.
 2: COMBINATION SMOKE CO2 DETECTORS WILL HAVE TO BE
 ADDED WITHIN 10’ OF ENTRANCE TO SLEEPING AREAS.
 3: A SERVICE OUTLET WILL HAVE TO BE ADDED WITHIN 25’ OF
 A/C CONDENSING UNITS.
 4: NOTE 6 ON FIREWALL DETAIL STATES “PERIMETER MAY BE
 CAULKED WITH SHEETROCK BRAND ACOUSTICAL SEALANT.”
 PERIMETER WILL HAVE TO BE CAULKED WITH FIRE RATED
 CAULK. REMOVE NOTE 6 AND ADD FIRE CAULK NOTE.
 5: ADD NOTE TO ELECTRICAL PAGE STATING THAT ALL
 ELECTRIC TO MEET NEC 2014. (ARC FAULT PROVISIONS AND
 DISHWASHERS AND WASHING MACHINES GFCI PROTECTED.)
 6: OUTLETS WILL NEED TO BE ADDED IN FRONT BEDROOMS BY
 CLOSETS TO PROVIDE OUTLET WITHIN 6’ OF DOOR ENTRY.
  
 PLEASE MAKE THESE ADDITIONS/CORRECTIONS TO PLANS ALONG
 WITH FIRE COMMENTS AND RESUBMIT PLANS FOR APPROVAL.
  
  
2018-07-23 15:27:08.00000THREE (3) SET OF PLAN SUBMITTED FOR REVIEW.

Review Stop ENGINEER SITE & DRAINAGE FDO
Rev No 1 Status A Date 07-23-2018 Cont ID  
Sent By nsulliva Date 07-23-2018 Time 16:29 Rev Time 0.00
Received By nsulliva Date 07-23-2018 Time 16:27 Sent To  
Notes
2018-07-23 16:30:29.00000PER D PETERSON ALREADY PERMITTED UNDER COMMERICAL
 DEVELOPMENT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status X Date 03-04-2019 Cont ID  
Sent By cshackel Date 06-20-2018 Time   Rev Time 0.00
Received By cshackel Date 07-23-2018 Time 15:27 Sent To  
Notes
2018-09-18 10:24:25.00000TO: ERIC LONGSHORE, BUILDING OFFICIAL
 FROM: JAMES E. BRANCA, SR., FIRE MARSHAL
 DATE: JUNE 20, 2018
 RE: ROYAL OAKS TRIPLEX 11, 12, 13, PERMIT # 18070555
 I HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, 6TH EDITION, AND NEED THE
 FOLLOWING ISSUES RESOLVED:
 1. THIS BUILDING IS REQUIRED TO HAVE A SUPERVISED
 AUTOMATIC FIRE SPRINKLER SYSTEM. (SEE LIFE SAFETY CODE
 30.3.5)
 2. SMOKE ALARMS MUST COMPLY WITH SECTION 30.3.4.5 AND
 9.6.2.10 OF THE LIFE SAFETY CODE.
 3. CARBON MONOXIDE ALARMS MUST COMPLY WITH SECTION
 30.3.4.6 OF THE LIFE SAFETY CODE.
 4. WALL SCHEDULES ARE NOT CLEARLY IDENTIFIED.
 5. THE “DEN” IN UNIT 2 NEEDS A SECONDARY MEANS OF
 ESCAPE TO COMPLY WITH SECTION 30.2.1.2 AND 24.2 OF THE
 LIFE SAFETY CODE.
 ALL REFERENCES TO THE LIFE SAFETY CODE ARE FOR THE
 FLORIDA SPECIFIC EDITION.
 PLEASE HAVE THE APPLICANT ADDRESS THESE ISSUES. IF
 THERE ARE ANY QUESTIONS I CAN BE REACHED AT
 863-385-1112
  
 30.2.1.2 MEANS OF ESCAPE WITHIN THE DWELLING UNIT SHALL
 COMPLY
 WITH THE PROVISIONS OF SECTION 24.2 FOR ONE- AND
 TWO-FAMILY
 DWELLINGS.
 24.2* MEANS OF ESCAPE REQUIREMENTS.
 24.2.1 GENERAL. THE PROVISIONS OF CHAPTER 7 SHALL NOT
 APPLY TO
 MEANS OF ESCAPE, UNLESS SPECIFICALLY REFERENCED IN THIS
 CHAPTER.
 24.2.2 NUMBER AND TYPES OF MEANS OF ESCAPE.
 24.2.2.1 NUMBER OF MEANS OF ESCAPE.
 24.2.2.1.1 IN DWELLINGS OR DWELLING UNITS OF TWO ROOMS
 OR MORE,
 EVERY SLEEPING ROOM AND EVERY LIVING AREA SHALL HAVE
 NOT LESS THAN
 ONE PRIMARY MEANS OF ESCAPE AND ONE SECONDARY MEANS OF
 ESCAPE.
 24.2.2.1.2 A SECONDARY MEANS OF ESCAPE SHALL NOT BE
 REQUIRED
 WHERE ONE OF THE FOLLOWING CONDITIONS IS MET:
 (1) THE BEDROOM OR LIVING AREA HAS A DOOR LEADING
 DIRECTLY TO THE
 OUTSIDE OF THE BUILDING AT OR TO THE FINISHED GROUND
 LEVEL.
 (2) THE DWELLING UNIT IS PROTECTED THROUGHOUT BY AN
 APPROVED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH 24.3.5.
 24.2.2.2 PRIMARY MEANS OF ESCAPE. THE PRIMARY MEANS OF
 ESCAPE SHALL BE A DOOR, STAIRWAY, OR RAMP PROVIDING A
 MEANS OF
 UNOBSTRUCTED TRAVEL TO THE OUTSIDE OF THE DWELLING UNIT
 AT STREET OR
 THE FINISHED GROUND LEVEL.
 24.2.2.3 SECONDARY MEANS OF ESCAPE. THE SECONDARY MEANS
 OF
 ESCAPE, OTHER THAN AN EXISTING APPROVED MEANS OF
 ESCAPE, SHALL BE
  
2018-07-23 15:28:13.00000TWO SET OF PLAN SENT TO COUNTY FIRE FOR REVIEW-CARRIER