Plan Review Details - Permit 18050783
Plan Review Stops For Permit 18050783
Review Stop BLDREN REISSUANCE BUILDING PERMIT
Rev No 1 Status A Date 08-15-2024 Cont ID  
Sent By shullett Date 08-15-2024 Time 08:11 Rev Time 0.00
Received By shullett Date 08-15-2024 Time 08:11 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 02-25-2019 Cont ID  
Sent By cshackel Date 02-25-2019 Time 08:08 Rev Time 0.00
Received By cshackel Date 05-31-2018 Time 10:09 Sent To  
Notes
***NONE***

Review Stop ENGINEER SITE & DRAINAGE FDO
Rev No 1 Status A Date 02-21-2019 Cont ID  
Sent By cshackel Date 01-31-2019 Time 08:22 Rev Time 0.00
Received By cshackel Date 05-31-2018 Time 10:09 Sent To  
Notes
2019-02-21 08:25:15.00000NEEDS ELEVATION CERTIFICATE.
2019-02-21 08:22:44.00000FINAL DEVELOPMENT ORDER & FLOOD HAZARD DEVELOPMENT
 APPROVED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date 02-25-2019 Cont ID  
Sent By cshackel Date 02-25-2019 Time 08:08 Rev Time 0.00
Received By cshackel Date 05-31-2018 Time 10:09 Sent To  
Notes
2019-02-18 13:14:12.000002/18/19 THREE (3) SET OF REVISED PLAN SUBMITTED FOR
 REVIEW-CARRIER ERIC LONGSHORE.
2018-08-16 13:13:00.00000MEMORANDUM
  
 TO: ERIC LONGSHORE, BUILDING OFFICIAL
 FROM: JAMES E. BRANCA, SR., FIRE MARSHAL
 DATE: AUGUST 16, 2018
 RE: FELLOWSHIP HALL PERMIT #18050783
 I HAVE REVIEWED THESE PLANS FOR COMPLIANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, SIXTH EDITION,
 AND HAVE FOUND THE FOLLOWING ISSUES:
  
 1. MISSING A SEATING PLAN OR PLANS. EACH PROPOSED
 SEATING ARRANGEMENT WILL NEED TO CONFORM TO
 SECTION 12.7.9 OF THE LIFE SAFETY CODE.
 2. THE PLANS DO NOT SHOW ANY DETAILS OF THE EXIT
 DISCHARGE TO A PUBLIC WAY. THE EXIT DISCHARGE
 WILL NEED TO CONFORM TO THE REQUIREMENTS OF SECTIONS
 7.7 AND 7.9 OF THE LIFE SAFETY CODE AND
 PROVIDE DRAWINGS OF ANY DIFFERENCES IN ELEVATIONS OUT
 TO A PUBLIC WAY.
 3. DRAFT STOPPING IS REQUIRED EVERY 3,000 FT2 PER
 SECTION 8.6.11 OF THE LIFE SAFETY CODE.
 4. THE PLANS SHOW A KITCHEN STOVE. THIS WILL NEED TO
 MEET THE REQUIREMENTS OF NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS,
 2014 EDITION.
  
 PLEASE HAVE THE APPLICANT ADDRESS THESE ISSUES.
  
 IF THE APPLICANT HAS ANY QUESTIONS I CAN BE REACHED AT
 863-385-1112
 HIGHLANDS COUNTY BOARD OF COUNTY COMMISSIONERS
 FIRE PREVENTION BUREAU
 6850 WEST GEORGE BOULEVARD
 SEBRING, FL 33875
 PHONE: 863-385-1112
 FAX: 863-402-7404
  

Review Stop ZONING ZONING DEPARTMENT
Rev No 1 Status A Date 02-25-2019 Cont ID  
Sent By cshackel Date 02-25-2019 Time 09:15 Rev Time 0.00
Received By cshackel Date 05-31-2018 Time 10:09 Sent To  
Notes
2019-02-25 08:11:00.00000NEEDS ZONING & PLANNING APPROVAL