-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 16110400
Plan Review Stops For Permit 16110400
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 03-21-2017 Cont ID  
Sent By cshackel Date 03-21-2017 Time 14:33 Rev Time 0.00
Received By cshackel Date 11-30-2016 Time 13:32 Sent To  
Notes
2017-02-06 16:47:50.000002/6/17 RECIEVED THREE (3) SETS OF PLANS (REVISIONS,
 ETC) CARRIER ERIC LONGSHORE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date   Cont ID  
Sent By   Date 03-14-2017 Time   Rev Time 0.00
Received By cshackel Date 11-30-2016 Time 13:32 Sent To  
Notes
2017-03-16 09:35:06.00000APPROVED, SEPARATE PERMITTING REQUIRED FOR FIRE ALARM
 AND FIRE SPRINKLER SYSTEM.
2017-01-17 16:00:57.00000I HAVE REVIEWED THESE PLANS IN ACCORDANCE WITH THE
 FLORIDA FIRE PREVENTION CODE AND WILL NEED THE
 FOLLOWING ISSUES ADDRESSED:
 1. CHANGE ALL ST. JOHNS COUNTY REFERENCE TO HIGHLANDS
 COUNTY.
 2. THE AUTOMATIC FIRE SPRINKLER SYSTEMS WILL NEED:
  FORWARD FLOW TEST PORT.
  FIRE DEPARTMENT CONNECTION AT THE BACKFLOW
 PREVENTER.
  UPDATED HYDRANT FLOW TEST DATA.
  FULL ENGINEERED PLANS WHICH INCLUDES THE
 LAYOUT, THE EXTENT OF COVERAGE FOR EACH SYSTEM, AND
 COVERAGE FOR THE CONCEALED COMBUSTIBLE SPACES.
  SEPARATELY PERMITTED FOR BOTH ABOVEGROUND AND
 UNDERGROUND WORK.
 3. FIRE ALARM SYSTEM WILL NEED:
  FULL PLANS WHICH INCLUDES THE EXTENT OF
 COVERAGE FOR EACH SYSTEM.
  SEPARATELY PERMITTED.
 4. EMERGENCY LIGHTING TO A PUBLIC WAY.

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved