-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 16070276
Plan Review Stops For Permit 16070276
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date 08-17-2016 Cont ID  
Sent By hlopez Date 08-17-2016 Time 09:56 Rev Time 0.00
Received By nsulliva Date 07-19-2016 Time 08:24 Sent To  
Notes
2016-08-17 08:13:46.00000JIMMY SENT EMAIL THAT REVISION WILL SUFFICE FOR FIRE
 REVIEW AND HE IS SENDING STAMPED PLANS BACK.
2016-08-05 14:11:04.00000JIMMY REVIEWED FOR CONFORMANCE WITH THE 2011 NFPA 96,
 STANDARD FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, THIS PLAN PROVIDES A
 CODE COMPLIANT CLEARANCE REDUCTION SYSTEM CONSISTING OF
 3M FIRE BARRIER DUCT WRAP 615+ FOR THE HOOD, GREASE
 REMOVAL DEVICES, EXHAUST FAN AND DUCT. HOWEVER, THERE
 ISN'T PROTECTION ON THE COMBUSTIBLE WALL FROM THE
 BOTTOM OF THE HOOD TO THE FLOOR AS REQUIRED IN SECTION
 4.2.4.3.

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved