Plan Review Details - Permit 14050192
Plan Review Stops For Permit 14050192
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 06-11-2014 Cont ID  
Sent By lmckinne Date 06-11-2014 Time   Rev Time 0.00
Received By lmckinne Date 05-14-2014 Time 15:00 Sent To  
Notes
2014-06-09 12:45:40.00000**HIT ATTACHMENT BUTTON FOR LETTER FROM ENGINEER
2014-06-09 09:31:34.00000JAMES BRANCA EMAIL TO CLAYTON JOHNSON:
 MR. JOHNSON, AN AMENDMENT LETTER WOULD BE FINE FOR THE
 INTERIOR FINISHES, OCCUPANT LOAD CALCULATIONS, AND THE
 ELECTRICAL PANELS. WHEN I RECEIVE THAT INFORMATION WE
 CAN MOVE FORWARD WITH THE PERMITTING PROCESS; HOWEVER,
 THE OWNERS WILL STILL NEED TO DECIDE ON THE TYPE OF
 COOKING OPERATIONS THEY WILL BE DOING AND THEN WE CAN
 SETTLE THAT ISSUE INDEPENDENTLY.
2014-06-09 09:27:10.00000CLAYTON JOHNSON RESPONSE
 I WILL GET THE LETTER PREPARED BY THE ARCHITECT AND
 EMAIL ON MONDAY, THEN FOLLOW WITH ORIGINALS.
  
 I HAVE SPOKEN WITH THE OWNER AND AWAIT AN ANSWER ON THE
 COOKING. I BELIEVE THE ANSWER WILL BE TO INSTALL THE
 COMMERCIAL HOOD SYSTEM, HOWEVER, I WILL VERIFY BY
 MONDAY.

Review Stop ENGINEER SITE & DRAINAGE FDO
Rev No 1 Status A Date 05-14-2014 Cont ID  
Sent By cshackel Date 05-14-2014 Time 15:00 Rev Time 0.00
Received By cshackel Date 05-14-2014 Time 14:24 Sent To  
Notes
2014-05-14 15:01:09.00000OK, NO S&D FINAL REQ

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date 06-10-2014 Cont ID  
Sent By cshackel Date 06-10-2014 Time 11:02 Rev Time 0.00
Received By cshackel Date 05-14-2014 Time 14:24 Sent To  
Notes
2014-06-06 15:23:04.00000I HAVE REVIEWED THESE PLANS ALONG WITH CONDUCTED A SITE
 VISIT FOR FIRE CODE COMPLIANCE AND HAVE THE FOLLOWING
 CONCERNS:
  
 1. THE INTERIOR FINISHES ARE MADE OF WOOD PANELING.
 2. THE RESIDENTIAL COOKING EQUIPMENT RANGE HOODS HAVE A
 GREASE BUILDUP WHICH DEMONSTRATES THE PRODUCTION OF
 GREASE LADEN VAPORS. IF THIS TYPE OF COOKING CONTINUES
 THEN THEY WILL BE CLASSIFIED AS COMMERCIAL AND NEED TO
 COMPLY WITH NFPA 96, VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 3. ELECTRICAL PANELS ARE LOCATED BEHIND STORAGE IN A
 CLOSET. (SEE PICTURE)
 4. THE PLANS DO NOT SHOW AN OCCUPANT LOAD CALCULATION.
  
  
 PLEASE HAVE THE APPLICANT ADDRESS THESE ISSUES BEFORE
 WE CONTINUE THE PERMITTING PROCESS.
  
  
 THANKS,
  
 JAMES E. BRANCA, SR.
 FIRE MARSHAL