Plan Review Details - Permit 14040404
Plan Review Stops For Permit 14040404
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 05-08-2014 Cont ID  
Sent By lmckinne Date 05-08-2014 Time 16:28 Rev Time 0.00
Received By lmckinne Date 04-28-2014 Time 12:14 Sent To  
Notes
***NONE***

Review Stop ENGINEER SITE & DRAINAGE FDO
Rev No 1 Status A Date 06-04-2014 Cont ID  
Sent By cshackel Date 06-04-2014 Time 16:19 Rev Time 0.00
Received By cshackel Date 04-28-2014 Time 12:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date 06-04-2014 Cont ID  
Sent By cshackel Date 06-04-2014 Time 16:19 Rev Time 0.00
Received By cshackel Date 04-28-2014 Time 12:14 Sent To  
Notes
2014-05-20 14:51:10.00000SY, THE HUMANE SOCIETY CONSTRUCTION PLANS DO NOT HAVE
 THE REQUIRED FIRE SPRINKLER SYSTEM LAYOUT INFORMATION.
 I HAVE CONTACTED THE ENGINEER OF RECORD AND HE
 RESPONDED WITH THE STATEMENT: "THE BUILDING IS TO BE
 PROVIDED WITH A FIRE SPRINKLER SYSTEM. THE DETAILED
 PLANS AND CALCULATIONS FOR THIS SYSTEM WILL BE PROVIDED
 BY THE FIRE SYSTEM SPECIALTY CONTRACTOR. THE BUILDING
 IS PROVIDED WITH A 6" CITY WATER SERVICE, WHICH SHOULD
 BE ADEQUATE FOR THE FIRE SPRINKLER SYSTEM." (I HAVE
 ATTACHED HIS WRITTEN RESPONSE TO THIS EMAIL).
  
  
 ***I AM STAMPING AND RETURNING THESE PLANS TO YOUR
 OFFICE; HOWEVER, I HAVE CONCERNS WITH THIS PROJECT
 PROCEEDING BEYOND THE INSTALLATION OF THE ?SLAB FORM
 BOARDS? UNTIL THEY HAVE SUBMITTED PLANS AND RECEIVED
 APPROVAL OF AN AUTOMATIC FIRE SPRINKLER SYSTEM. UNLESS
 ALL PARTIES FULLY UNDERSTAND THE LOGISTICS OF PROVIDING
 THIS SYSTEM, IT IS MY RECOMMENDATION TO WITHHOLD THE
 PERMIT UNTIL SPRINKLER PLANS ARE SUBMITTED FOR
 PERMITTING.
2014-05-19 16:47:34.00000MR. STUHRKE, IN REFERENCE TO THE PLANS SUBMITTED FOR
 PERMITTING OF THE HUMANE SOCIETY, THE FOLLOWING ISSUES
 NEED TO BE ADDRESSED:
  
 ? DRAFT STOPPING IS REQUIRED EVERY 3,000 FT2
 ? THE COVER PAGE INDICATES THE BUILDINGS WILL HAVE FIRE
 SPRINKLERS; HOWEVER, THERE IS NOT A SPRINKLER LAYOUT
 PLAN OR INDICATION OF AN ADEQUATE WATER SUPPLY.
 ? THE CAT FACILITY PLANS ARE INCOMPLETE.
  
 ONCE THESE ISSUES ARE PROPERLY ADDRESSED I WILL SEND
 THESE PLANS BACK TO THE BUILDING DEPARTMENT TO CONTINUE
 THE PERMITTING PROCESS.