Plan Review Details - Permit 12070078
Plan Review Stops For Permit 12070078
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 07-13-2012 Cont ID  
Sent By lmckinne Date 07-13-2012 Time 16:05 Rev Time 0.00
Received By lmckinne Date 07-10-2012 Time 12:19 Sent To  
Notes
2012-07-10 12:20:01.00000LMM HAS TO APPROVE

Review Stop ETRANSPCON TRANSPORTATION CONCURRENCY
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date 08-09-2012 Time   Sent To  
Notes
2012-08-10 10:15:48.00000REC. EMAIL FROM J BRANCA - RELEASED TO PERMIT - PLANS
 APPROVED
2012-07-25 11:30:43.00000JIMMY BRANCA REQUEST FOR ADDITIONAL INFORMATION: 1.
 FIRE EXTINGUISHERS ARE REQUIRED (LSC 38.3.5), 2. EGRESS
 IS NOT ALLOWED THROUGH STORAGE ROOM (LSC 7.5.2.1), 3.
 THE PLANS INDICATE AN ACCESS CARD READER SYSTEM. THERE
 ARE INSUFFICIENT DETAILS TO ENSURE COMPLIANCE WITH THE
 LSC 7.2.1.6.2
 4. INSUFFICIENT DETAIL FOR EGRESS DOORS. (DOOR SIZE
 AND LOCKING/LATCHING HARDWARE) LSC 38.2.2 5. THE
 PLANS DO NOT SHOW ILLUMINATION OF MEANS OF EGRESS TO
 THE EXIT DISCHARGE. LSC 38.2.8. AND LSC 7.8 6. IF
 THERE WILL BE AN HVAC SYSTEM INSTALLED THERE WILL NEED
 TO BE PLANS INDICATING THE SYSTEM WILL COMPLY WITH LSC
 38.5.2 AND LSC 9.2.
2012-07-10 12:21:20.00000SY DID FIRE TRACKING SHEET & TAKING PLANS TO FIRE