Plan Review Details - Permit 11080256
Plan Review Stops For Permit 11080256
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 09-06-2011 Cont ID  
Sent By lmckinne Date 09-06-2011 Time 12:31 Rev Time 0.00
Received By lmckinne Date 08-29-2011 Time 14:58 Sent To  
Notes
2011-09-06 12:30:17.000001.ATTIC DRAFTSTOP NOT TO EXCEED 3'000 SQ FT 717.4.3
 FBC ----2. 517.13 NEC ELECT TO BE IN EMT.----3. NEED
 2/0 GRNDG. ELECTRODE CONDUCTOR TABLE 250.66

Review Stop ENGINEER SITE & DRAINAGE FDO
Rev No 1 Status A Date 09-30-2011 Cont ID  
Sent By cshackel Date 09-30-2011 Time 09:04 Rev Time 0.00
Received By cshackel Date 08-29-2011 Time 14:58 Sent To  
Notes
2011-09-30 09:05:19.00000CONDITIONAL APPROVAL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date 08-31-2011 Cont ID  
Sent By hmckinne Date 08-31-2011 Time 11:59 Rev Time 0.00
Received By hmckinne Date 08-29-2011 Time 14:58 Sent To  
Notes
2011-12-19 12:39:47.00000RECEIVED APPROVED REVISED PLANS FROM SNL FIRE, RYAN.
 12/19/2011
2011-10-10 09:39:09.00000SNL FIRE

Review Stop ZONING ZONING DEPARTMENT
Rev No 1 Status A Date 10-17-2011 Cont ID  
Sent By cshackel Date 10-10-2011 Time 09:39 Rev Time 0.00
Received By mbryant Date 08-29-2011 Time 09:39 Sent To  
Notes
2011-10-10 09:40:16.00000WE HAVE COPY OF APPLICATION, NOT THE ORIGINAL.. IT WAS
 SIGNED OFF BY ZONING AS APPROVED FOR PLANS REVIEW ONLY.