-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 10090246
Plan Review Stops For Permit 10090246
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 11-18-2010 Cont ID  
Sent By lmckinne Date 11-18-2010 Time 09:11 Rev Time 0.00
Received By lmckinne Date 09-21-2010 Time 08:58 Sent To  
Notes
2011-01-21 09:52:56.00000CONTRACTOR PICKED UP THEIR JOB-SITE PLAN AND THE EXTRA
 PLAN TO TAKE TO MEETING @ SITE 1/21/11, THEY WILL BE IN
 W/SIGNED CONTRACT NEXT WEEK.
2010-12-13 12:39:14.00000RECEIVED ENERGY FORM 12/13/10
2010-11-18 15:06:53.00000NEED ENERGY FORMS
2010-11-18 09:13:37.00000RECIEVED REVISIONS 11-15-10 APPROVED 11-18-10
2010-09-23 14:40:40.000001.F-1 CONLICTED EXIT LIGHTING 2.PAGE S-2 FT-2 FOOTING
 PAGE CONFLICTS WITH S-3 .3 ON #5 OR #6 BARS IN FTG.
 3.NEED 3/0 GRDG. ELECT. CONDUCTORS 600 AMP TO GRD. ROD

Review Stop ENGINEER SITE & DRAINAGE FDO
Rev No 1 Status A Date   Cont ID  
Sent By   Date 10-29-2010 Time   Rev Time 0.00
Received By hmckinne Date 09-21-2010 Time 08:59 Sent To  
Notes
2010-11-15 11:20:31.00000ENGINEERING LETTER APPROVES FINAL DEVELOPMENT ORDER
 WITH CONDITION THAT CO WILL NOT BE ISSUED UNTIL THEY
 RECEIVE APPROVED FDOT DRAINAGE PERMIT AND THE REVISED
 WATER MANAGEMENT DISTRICT PERMIT AND ASSOCIATED PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date 10-11-2010 Cont ID  
Sent By cshackel Date 10-11-2010 Time 12:05 Rev Time 0.00
Received By cshackel Date 09-21-2010 Time 08:59 Sent To  
Notes
2010-11-18 09:17:46.00000S-N-L FIRE APPROVED 10-11-10

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved