INSPECTION DETAILS FOR PERMIT 16020105
Permit Number 16020105 Owner Name SUN COMM ACQUISITIONS LLC
Permit Type MECHANICAL Permit Address 436 SWAN DR
Inspection Type MECHANICAL FINAL-2 City/State/Zip SEBRING, FL 33872
Inspect Area SE Inspector ERIC
Request Date 03-08-2016 Scheduled Date 03-11-2016
Instructions EARLY PLEASE
Contact Info  
Contractor HC02869 Inspect Date 03-11-2016
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7223455
Fee ID BRI
Inspector Notes
Date Text
2016-03-11 15:25:28.000001] BRANCH CIRCUIT HAS 70A BRKR; CANNOT BE MORE THAN 60A
 PER NAMEPLATE
 2] CONDUCTORS IN FLEXIBLE CONDUIT BETWEEN DISCONNECT
 AND UNIT ARE #8 COPPER; SHOULD BE #6 FOR THIS CIRCUIT.
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved