-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Inspection Details
INSPECTION DETAILS FOR PERMIT 23080813
Permit Number 23080813 Owner Name CABANILLA MARK R NILDA G
Permit Type EPUMP Permit Address 4065 CR 64 E
Inspection Type PUMP SERVICE-2 City/State/Zip AVON PARK, FL 33825
Inspect Area   Inspector JOHNK
Request Date 07-03-2024 Scheduled Date 07-05-2024
Instructions MAYBE ELEC SERVICE CHANGE/ PREV NOTES
Contact Info  
Contractor HC00859-02 Inspect Date 07-05-2024
Result F Fail Code  
Comments SEE NOTES
Work Time   Confirmation Number 7384017
Fee ID  
Inspector Notes
Date Text
2024-07-05 15:34:00.000001) BUILD THE SERVICE ON A PERMANENT SERVICE POLE.
 2) SUPPORT THE SERVICE DROP WITH A POINT OF ATTACHMENT
 INSTALLED ON THE POLE ITSELF.
 3) PROVIDE AN APPROVED METHOD FOR VERIFICATION OF THE
 UNDERGROUND WORK BETWEEN THE SERVICE AND THE WELL.
 4) INSTALL A SECOND GROUND ROD.
 *** DISREGARD THE FIELD NOTES REQUIRING A SERVICE OCPD;
 THIS PERMIT WAS PULLED IN 2023 AND NEC 2017 APPLIES.
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved