INSPECTION DETAILS FOR PERMIT 24040599
Permit Number 24040599 Owner Name ORTIZ JIMMY J
Permit Type ESERVICE Permit Address 6005 HAZEL RD
Inspection Type ELECTRIC SERVICE-2 City/State/Zip SEBRING, FL 33875-
Inspect Area   Inspector JOHNK
Request Date 07-25-2024 Scheduled Date 07-26-2024
Instructions  
Contact Info  
Contractor OWNER Inspect Date 07-26-2024
Result F Fail Code  
Comments SEE NOTES
Work Time   Confirmation Number 7385338
Fee ID BRI
Inspector Notes
Date Text
2024-07-29 16:48:41.000001) THE SERVICE CONDUCTORS ARE UNDERSIZED FOR A 200-AMP
 MAIN BREAKER PANEL. (FED WITH #2 CU)
 2) INSTALL THE BONDING SCREW IN THE DISTRIBUTION PANEL.
 3) BOND THE BUILDING STRUCTURE TO THE GROUNDING
 ELECTRODE.
 4) INSTALL A SECOND GROUND ROD A MINIMUM OF 6' FROM THE
 OTHER GROUND ROD.
 5) INSTALL A GFCI PROTECTED RECEPTACLE FOR EACH GARAGE
 BAY.
 6) COMPETE THE PANEL SCHEDULE.