-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Inspection Details
INSPECTION DETAILS FOR PERMIT 23060130
Permit Number 23060130 Owner Name MILLER HERMAN F
Permit Type SOLAR Permit Address 4607 SUNBEAM ST
Inspection Type FINAL-2 City/State/Zip SEBRING, FL 33872-
Inspect Area   Inspector CHUCK
Request Date 07-06-2023 Scheduled Date 07-07-2023
Instructions OWNER HOME ALL DAY
Contact Info  
Contractor HC04427 Inspect Date 07-07-2023
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7359598
Fee ID BRI
Inspector Notes
Date Text
2023-07-07 12:36:23.000001] REMOVE UNNECESSARY AND NON-APPLICABLE FIELD LABELS
 (MARKED WITH "X" BY INSPECTOR). LABELS SHOULD BE
 AFFIXED ONLY WHERE SPECIFICALLY REQUIRED BY NEC,
 PARTICULARLY ARTICLES 690 & 705.
 2] INSTALL MIN #8 CU EQUIPMENT GROUNDING CONDUCTOR
 BETWEEN NEW 200A PANEL AND PV DISCONNECT, AND USE THIS
 CONDUCTOR TO PROVIDE BONDING OF PV DISCONNECT. BECAUSE
 THE INTERCONNECTION ORIGINATES AT A FEEDER TAP, THE
 NEUTRAL CANNOT BE USED FOR BONDING OF THE PV SYSTEM
 (REMOVE NEUTRAL BONDING SCREW IN PV DISCONNECT).
 CONTACT INSPECTOR REGARDING QUESTION ABOUT ADDING NEW
 EXTERIOR LOAD CENTER.