INSPECTION DETAILS FOR PERMIT 21120481
Permit Number 21120481 Owner Name PIOCNACIA RACHEL + JAMESON G
Permit Type SOLAR Permit Address 3829 RAMIRO ST
Inspection Type FINAL-2 City/State/Zip SEBRING, FL 33872
Inspect Area   Inspector CHUCK
Request Date 03-31-2022 Scheduled Date 04-01-2022
Instructions  
Contact Info  
Contractor HC04427 Inspect Date 04-01-2022
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7316131
Fee ID BRI
Inspector Notes
Date Text
2022-04-01 13:33:30.00000IN THE EXTERIOR PV DISCONNECT, A BOND STILL EXISTS
 BETWEEN THE NEUTRAL AND THE EQUIPMENT GROUND. THESE TWO
 CONDUCTORS MUST BE ELECTRICALLY SEPARATE. 250.24
 (A)(5).