-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Inspection Details
INSPECTION DETAILS FOR PERMIT 21120475
Permit Number 21120475 Owner Name RENDA FRANCESCO J
Permit Type SOLAR Permit Address 2754 NAUTILUS DR
Inspection Type FINAL-2 City/State/Zip AVON PARK, FL 33825
Inspect Area AP Inspector CHUCK
Request Date 02-17-2022 Scheduled Date 02-18-2022
Instructions  
Contact Info  
Contractor HC04427 Inspect Date 02-18-2022
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7313332
Fee ID BRI
Inspector Notes
Date Text
2022-02-18 14:25:42.000001] EQUIPMENT GROUNDING CONDUCTOR (#8) BETWEEN INTERIOR
 AND EXTERIOR DISCONNECTS IS UNDERSIZED FOR 110A
 OVERCURRENT PROTECTION; MUST BE MINIMUM #6 [TABLE
 250.122]. WHEN REPLACING, EQUIPMENT GROUNDING
 CONDUCTORS MUST BE INSTALLED IN THE SAME RACEWAY/CABLE
 AS OTHER CIRCUIT CONDUCTORS.
 2] REPLACE NM CABLE USED BETWEEN SUPPLY-SIDE TAP AND PV
 FUSIBLE DISCONNECT. WIRING METHOD MUST COMPLY WITH A
 TYPE LISTED IN 230.43 (SAME AS SERVICE CONDUCTORS).
 3] REPLACE ALL PANEL COVER SCREWS WITH SHORTER
 MACHINE-THREAD TYPE. 2" SHEET METAL SCREWS NOT APPROVED
 DUE TO POTENTIAL CONDUCTOR DAMAGE. [110.3, 110.12]
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved