INSPECTION DETAILS FOR PERMIT 22061226
Permit Number 22061226 Owner Name MORO GENESIS N
Permit Type BRNBLMONO Permit Address 2062 N OLIVIA DR
Inspection Type TUG INSPECTION-1 City/State/Zip AVON PARK, FL 33825
Inspect Area AP Inspector CHUCK
Request Date 10-07-2022 Scheduled Date 10-10-2022
Instructions  
Contact Info  
Contractor OWNER Inspect Date 10-10-2022
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7334581
Fee ID BRI
Inspector Notes
Date Text
2022-10-10 15:55:55.000001] SERVICE NOT CONFIGURED FOR TUG
 2] METER TERMINALS INCORRECTLY CONNECTED
 3] GROUNDING ELECTRODE CONDUCTOR MUST BE TIGHTED UNDER
 TERMINAL SCREW
 4] INSTALL CLOSURE PLATE TOP OF METER ENCLOSURE
 5] REMOVE GROUNDING CONDUCTOR BETWEEN METER AND GARAGE
 PANEL (BONDING IS ACCOMPLISHED THRU NEUTRAL).