-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Inspection Details
INSPECTION DETAILS FOR PERMIT 20030351
Permit Number 20030351 Owner Name PATEL HETAL D
Permit Type EADDITION Permit Address 1010 W WALNUT ST
Inspection Type SERVICE CHANGE-1 City/State/Zip AVON PARK, FL 33825
Inspect Area   Inspector CHUCK
Request Date 03-17-2020 Scheduled Date 03-18-2020
Instructions AM - PLEASE
Contact Info  
Contractor HC00767 Inspect Date 03-18-2020
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7280232
Fee ID BRI
Inspector Notes
Date Text
2020-03-18 10:38:00.000001] GROUNDING ELECTRODE CONDUCTOR MUST BE MIN #6 CU FOR
 THIS APPLICATION. STRAP TO WALL.
 2] STRAP RISER TO WALL
 3] REMOVE GREEN CONDUCTOR BETWEEN METER AND PANEL
 4] ATTACH BONDING STRAP IN PANEL
 5] #10 NM CABLE CANNOT BE FUSED AT 40 AMPS; MAX OCPD =
 30A
 6] #12 NM CABLE CANNOT BE FUSED AT 30 AMPS; MAX OCPD =
 20A
 7] CABLE SHEATHS MUST ENTER PANEL MIN 1/4" (BOTTOM OF
 PANEL)
 8] LABEL PANEL AS MUCH AS POSSIBLE
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved