-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Inspection Details
INSPECTION DETAILS FOR PERMIT 15120072
Permit Number 15120072 Owner Name MONTANEZ MILTON
Permit Type ERECONNECT Permit Address 2690 US 27
Inspection Type RECONNECTION OF SERVICE-1 City/State/Zip LAKE PLACID, FL 33852
Inspect Area LP Inspector CHUCK
Request Date 12-11-2015 Scheduled Date 12-14-2015
Instructions  
Contact Info  
Contractor   Inspect Date 12-14-2015
Result F Fail Code  
Comments  
Work Time   Confirmation Number 145857
Fee ID  
Inspector Notes
Date Text
2015-12-14 11:02:02.000001] NEEDS GROUND CLAMP
 2] CONTROL CONDUCTORS REQUIRE OVERCURRENT PROTECTION.
 #12 AND #14 AWG CONDUCTORS EXTENDING BEYOND CONTROL
 ENCLOSURE ARE NOT PROTECTED BY THE 100 AMP BREAKER.
 SEE TABLE 430.72 (B).