Inspection Details
INSPECTION DETAILS FOR PERMIT 24020007
Permit Number 24020007 Owner Name H H SAMUEL PROPERTIES LLC
Permit Type BRNBLMONO Permit Address 6800 CORAL RIDGE RD
Inspection Type PRE-POWER ELECTRIC-1 City/State/Zip SEBRING, FL 33876-
Inspect Area   Inspector JOHNK
Request Date 07-29-2024 Scheduled Date 07-30-2024
Instructions  
Contact Info  
Contractor HC05960 Inspect Date 07-30-2024
Result F Fail Code  
Comments HOME OPEN; SEE NOTES
Work Time   Confirmation Number 7385525
Fee ID BRI
Inspector Notes
Date Text
2024-07-30 16:57:51.000001) CONNECT THE DISTRIBUTION PANEL FEEDERS AT THE
 SERVICE.
 2) REMOVE THE STUCCO ENCASING THE INTERSYSTEM BONDING
 BRIDGE TO ALLOW PROPER FUNCTION.
 3) THE DRYER CIRCUIT MUST BE GFCI PROTECTED.
 4) BRANCH CIRCUIT #12, "KITCHEN RECEPTACLES" MUST BE
 BOTH GFCI & AFCI PROTECTED.
 5) PROPERLY LABEL BRANCH CIRCUIT #14, "GDO" - THE CABLE
 JACKET SHOWS IT AS THE "STUDY".
 6) THE BRANCH CIRCUITS FOR THE TANKLESS WATER HEATER
 ARE NOT INSTALLED; IT WILL REQUIRE THREE 40-AMP 240
 VOLT BRANCH CIRCUITS.
 7) THE 2-POLE 30-AMP CIRCUIT BREAKER LABELED "SPARE"
 HAS A BRANCH CIRCUIT CONNECTED AND IT'S NOT CLEAR IF IT
 IS TERMINATED; REMOVE AND CAP-OFF THIS CIRCUIT.