-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Inspection Details
INSPECTION DETAILS FOR PERMIT 22040351
Permit Number 22040351 Owner Name FIRST SIGHT REAL ESTATE, LLC
Permit Type BRNBLMONO Permit Address 6224 CANDLER TER
Inspection Type PRE-POWER ELECTRIC-1 City/State/Zip SEBRING, FL 33876
Inspect Area   Inspector CHUCK
Request Date 11-14-2022 Scheduled Date 11-15-2022
Instructions  
Contact Info  
Contractor HC04582 Inspect Date 11-15-2022
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7338270
Fee ID  
Inspector Notes
Date Text
2022-11-15 15:25:15.000001] INSTALL ADDRESS NUMBERS ON BUILDING
 2] HANDWRITTEN "7KW" MARKING ON AIR HANDLERS DOES NOT
 CORRESPOND WITH ACTUAL INSTALLED HEAT SIZE (8 KW). THE
 FACTORY LABEL IS SUFFICIENT; MARKING WITH SHARPIE NOT
 NECESSARY, BUT MUST BE CORRECT.
 3] IF 8 KW HEAT IS USED, CHANGE AIR HANDLER BREAKERS TO
 50A. EXISTING 40A BREAKERS ARE APPROVED IF HEAT IS
 CHANGED TO 7 KW.
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved