-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Inspection Details
INSPECTION DETAILS FOR PERMIT 23110666
Permit Number 23110666 Owner Name DAVIS LARRY WESLEY JR
Permit Type ESERVICE Permit Address 2015 CARROLL SHELBY RD
Inspection Type ELECTRIC SERVICE-1 City/State/Zip SEBRING, FL 33876
Inspect Area   Inspector JOHNK
Request Date 02-28-2024 Scheduled Date 02-29-2024
Instructions  
Contact Info  
Contractor   Inspect Date 02-29-2024
Result F Fail Code  
Comments SEE NOTES
Work Time   Confirmation Number 7375530
Fee ID  
Inspector Notes
Date Text
2024-02-29 16:35:34.000001) BOND THE TROUGH TO THE SERVICE GROUND.
 2) INSTALLL BONDING BUSHING ON THE CLOSE NIPPLE BETWEEN
 THE TROUGH AND ATS.
 3) REMOVE THE BONDING SCREWS FROM THE BREAKER
 DISCONNECTS FOR PANEL A & PANEL B.
 4) RELOCATE THE GROUND IN THE BARN DISCONNECT FROM THE
 NEUTRAL BAR TO A GROUND BAR OR GROUND LUG.
 NOTE: NEUTRALS AND GROUNDS MUST BE SEPARATED AFTER THE
 FIRST MEANS OF DISCONNECT FOR THE SERVICE.