-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Inspection Details
INSPECTION DETAILS FOR PERMIT 17050274
Permit Number 17050274 Owner Name SMITH EARL K JR
Permit Type ESERVICE Permit Address 1153 LAKE HILL DR
Inspection Type ELECTRIC SERVICE-1 City/State/Zip LAKE PLACID, FL 33852
Inspect Area LP Inspector CHUCK
Request Date 05-16-2017 Scheduled Date 05-17-2017
Instructions  
Contact Info  
Contractor   Inspect Date 05-17-2017
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7235857
Fee ID  
Inspector Notes
Date Text
2017-05-17 14:00:33.000001] NEED MAIN BONDING JUMPER IN LOAD CENTER
 2] 4 X 4 IS NOT STRUCTURALLY ADEQUATE FOR PERMANENT
 SERVICE; REPLACE POLE, BRACE, OR INSTALL ADDITIONAL
 BASE SUPPORT (POLE IS LESS THAN TEN FEET FROM UTILITY
 DROP POLE).