INSPECTION DETAILS FOR PERMIT 17010519
Permit Number 17010519 Owner Name MARANAN ABELLA
Permit Type ESERVICE Permit Address 15 LAKE BYRD BLVD
Inspection Type ELECTRIC SERVICE-1 City/State/Zip AVON PARK, FL 33825
Inspect Area   Inspector CHUCK
Request Date 01-30-2017 Scheduled Date 01-31-2017
Instructions AM INSP-CALL 30 MINS PRIOR
Contact Info 718-838-0797 ABELLA
Contractor   Inspect Date 01-31-2017
Result I Fail Code  
Comments  
Work Time   Confirmation Number 7232581
Fee ID  
Inspector Notes
Date Text
2017-01-31 14:12:10.00000IN-PROGRESS INSPECTION; PRIOR TO POWER RELEASE:
 1] INSTALL APPROVED LUG FOR FEEDER EQUIPMENT GROUNDING
 CONDUCTOR IN SERVICE PANEL.
 2] SEPARATE EQUIPMENT GROUNDING CONDUCTORS AND NEUTRALS
 AT INTERIOR PANEL.
 3] REMOVE OLD SERVICE FROM HOUSE. ALL TEMPORARY
 CONSTRUCTION POWER MUST ORIGINATE FROM OUTLETS OUTSIDE
 THE HOUSE (THERE IS AN ACTIVE POLE SERVICE IN THE BACK
 YARD). REMOVE THE BACKFED EXTENSION CORD FROM THE
 JOBSITE.
 4] COMPLETE ALL INTERIOR ROUGH-IN WIRING AND CAP ALL
 OPEN CONDUCTORS.