INSPECTION DETAILS FOR PERMIT 16070278
Permit Number 16070278 Owner Name SUN N LAKE OF SEBRING IMP DIST
Permit Type ESERVICE Permit Address 4710 DARNELL DR
Inspection Type ELECTRIC SERVICE-1 City/State/Zip SEBRING, FL 33872
Inspect Area AP Inspector CHUCK
Request Date 07-20-2016 Scheduled Date 07-21-2016
Instructions  
Contact Info  
Contractor   Inspect Date 07-21-2016
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7227385
Fee ID  
Inspector Notes
Date Text
2016-07-21 16:01:01.000001] BACKFED MAIN BREAKER REQUIRES A RETAINING DEVICE
 408.36 (D)
 2] TWO 20A SINGLE POLE BREAKERS REQUIRE A HANDLE TIE OR
 REPLACEMENT WITH A TWO-POLE BREAKER (MULTIWIRE CIRCUIT)
 210.4 (B)
 3] INSTALL BONDING BUSHING ON ONE END OF OFFSET NIPPLE
 BETWEEN METER AND PANEL 250.92
 4] REMOVE LATTICE IN FRONT OF SERVICE. MINIMUM 36"
 CLEARANCE REQUIRED. 110.26