-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Inspection Details
INSPECTION DETAILS FOR PERMIT 16070085
Permit Number 16070085 Owner Name REYNOLDS CHARLES L JR + ANNE D
Permit Type ESCHANGE Permit Address 8855 TWITTY RD
Inspection Type CHECK STATUS-1 City/State/Zip SEBRING, FL 33876
Inspect Area   Inspector CHUCK
Request Date 07-11-2016 Scheduled Date 07-11-2016
Instructions  
Contact Info  
Contractor HC00814 Inspect Date 07-11-2016
Result I Fail Code  
Comments REQUESTED BY OWNER
Work Time   Confirmation Number 7227164
Fee ID  
Inspector Notes
Date Text
2016-07-11 16:31:23.000001] NEUTRAL SHOULD BE MARKED WHITE AT WEATHERHEAD;
 REMOVE WHITE TAPE FROM UNGROUNDED SERVICE CONDUCTOR.
 2] MARK HIGH-LEG WITH ORANGE TAPE AT WEATHERHEAD, IN
 METER CAN, AND IN SERVICE DISCONNECT ENCLOSURE
 (CURRENTLY IS MARKED RED).
 3] HIGH-LEG MUST BE TERMINATED ON C PHASE IN METER CAN
 AND ON B PHASE AT LINE SIDE OF SERVICE BREAKER.
 4] INSTALL BONDING BUSHING ON 2" NIPPLE BETWEEN METER
 CAN AND SERVICE DISCONNECT ENCLOSURE AND CONNECT TO
 GROUND WITH #4 COPPER.
 5] INSTALL PERMANENT ADDRESS LABEL ON FACE OF METER
 CAN.
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved