-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Inspection Details
INSPECTION DETAILS FOR PERMIT 23080221
Permit Number 23080221 Owner Name TANGLEWOOD MHC LLC
Permit Type BCMISC Permit Address 523 WILDERNESS CIR
Inspection Type SLAB-1 City/State/Zip SEBRING, FL 33872
Inspect Area   Inspector DAVID
Request Date 10-09-2023 Scheduled Date 10-10-2023
Instructions  
Contact Info  
Contractor 304-01 Inspect Date 10-10-2023
Result F Fail Code  
Comments SEE NOTES
Work Time   Confirmation Number 7366129
Fee ID  
Inspector Notes
Date Text
2023-10-10 15:15:32.00000FOOTERS ARE WRONG SIZE
 NO PLANS ON SITE
 CONTRACTOR TEXTED A PICTURE OF FOOTER DIMENSIONS
 FOOTERS MUST BE 16"X 16" W/ 2 #4 REBAR CONT.
 16" DEPTH DOES NOT INCLUDE THE 1 1/2 " OF RECESS FOR
 SIDING
 TOTAL DEPTH OF FOOTER SHOULD BE 17 1/2 " FROM TOP OF
 FORM BOARD
  