INSPECTION DETAILS FOR PERMIT 21020020
Permit Number 21020020 Owner Name BURKE THOMAS M + GRACE A
Permit Type BRMISC Permit Address 123 MURRAY CT NW
Inspection Type PRELATH ELECTRIC-1 City/State/Zip LAKE PLACID, FL 33852
Inspect Area LP Inspector CHUCK
Request Date 04-09-2021 Scheduled Date 04-12-2021
Instructions  
Contact Info  
Contractor HC00765 Inspect Date 04-12-2021
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7296606
Fee ID  
Inspector Notes
Date Text
2021-04-12 14:41:22.000001] FOAM AROUND BOX IN MIDDLE BEDROOM, EXTERIOR WALL,
 AND BELOW 4-GANG BOX AT FRONT ENTRY
 2] SECURE ATTIC JUNCTION BOX ABOVE DINING ROOM. CABLE
 SHEATHS MUST FULLY ENTER BOX; BOX MUST BE SECURED SO
 ACCESSIBLE AFTER INSULATION BLOWN IN.
 3] REMOVE 14/2 CABLE CAPPED OFF IN WALL, JUST INSIDE
 FRONT DOOR IN WALL BETWEEN GARAGE & LIVING ROOM.
 4] REPLACE CONDUCTORS INSTALLED IN SLAB CONDUIT TO
 KITCHEN HALF WALL. CONDUCTORS MUST BE LISTED FOR WET
 LOCATION; NM CABLE NOT APPROVED FOR THIS APPLICATION.
 SEE 310.10 (C) & DEFINITION OF WET LOCATION IN ARTICLE
 100.