INSPECTION DETAILS FOR PERMIT 22111282
Permit Number 22111282 Owner Name DICKEY DARRY M
Permit Type SOLAR Permit Address 41 INDIGO DR
Inspection Type FINAL-1 City/State/Zip LAKE PLACID, FL 33852
Inspect Area   Inspector CHUCK
Request Date 04-11-2023 Scheduled Date 04-17-2023
Instructions HOMEOWNER WILL BE HOME FOR ACCESS.
Contact Info 689-221-7002
Contractor   Inspect Date 04-17-2023
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7352466
Fee ID BRI
Inspector Notes
Date Text
2023-04-17 14:26:29.000001] WIREWAY MUST BE DIRECTLY BONDED TO EQUIPMENT
 GROUNDING CONDUCTOR FROM SERVICE PANEL. INSTALL
 GROUNDING LUG WITH BOLT & NUT; MAINTAIN GROUNDING
 CONTINUTITY TO ALL COMPONENTS.
 2] REPLACE LOWER LEFT COVER SCREW ON BACKUP INTERFACE
 ENCLOSURE. ALLEN SCREW HEAD IS STRIPPED OUT.