-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Inspection Details
INSPECTION DETAILS FOR PERMIT 22100019
Permit Number 22100019 Owner Name GREEN JEREMY S
Permit Type SOLAR Permit Address 2745 W SHULA RD
Inspection Type FINAL-1 City/State/Zip AVON PARK, FL 33825
Inspect Area AP Inspector CHUCK
Request Date 03-16-2023 Scheduled Date 03-20-2023
Instructions  
Contact Info 4074562743
Contractor   Inspect Date 03-20-2023
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7350186
Fee ID BRI
Inspector Notes
Date Text
2023-03-20 14:44:50.000001] INSTALL SUPPLY-SIDE CONDUCTORS IN SEPARATE RACEWAY;
 DO NOT INSTALL WITH FEEDER CONDUCTORS OR PASS THROUGH
 TESLA SWITCH, 230.7, 312.8 (A)(3)
 2] INSTALL MIN #10 EQUIP GRND CONDUCTOR WITH PV STRING
 CONDUCTORS BETWEEN ENPHASE COMBINER PANEL AND NEW EATON
 PANEL ON LEFT SIDE OF COMBINER, 300.3 (B).
 3] RE-IDENTIFY BREAKER SPACES IN EXISTING GARAGE PANEL
 WHERE CIRCUITS HAVE BEEN RELOCATED TO BACKUP PANEL,
 408.4 (A)
 4] INDENTIFY TOP 150A BRKR IN SERVICE PANEL BELOW METER
 AS "SERVICE DISCONNECT", 230.70 (B)
 5] TWO UNGROUNDED ("HOT") CONDUCTORS SUPPLYING NEW
 BACKUP PANEL ARE NOT SUBJECT TO DERATING AND MUST BE
 FULLY SIZED FOR 150A PER TABLE 310.15 (B)(16). USE MIN
 1/0 CU.
2022-10-04 08:10:02.00000DROPPED OFF
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved