INSPECTION DETAILS FOR PERMIT 22041049
Permit Number 22041049 Owner Name GALLAGHER JAY R
Permit Type SOLAR Permit Address 4717 SILVER PALM DR
Inspection Type FINAL-1 City/State/Zip SEBRING, FL 33870
Inspect Area SE Inspector CHUCK
Request Date 06-09-2022 Scheduled Date 06-10-2022
Instructions CALL ON THE WAY
Contact Info 8135408807
Contractor   Inspect Date 06-10-2022
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7321381
Fee ID BRI
Inspector Notes
Date Text
2022-06-10 15:49:33.000001] APPROVED PLANS/PERMIT CARD NOT ON JOBSITE
 2] #10 EQUIPMENT GROUNDING CONDUCTOR TO COMBINER PANEL
 DOES NOT PROVIDE AN EFFECTIVE PATH; CONNECT TO
 GROUNDING CONDUCTOR FROM TESLA SWITCH WITHIN FUSED PV
 DISCONNECT, NOT JUST TO BONDING BUSHING.
 3] LABEL BREAKERS IN TESLA SWITCH: SERVICE DISCONNECT,
 BATTERY, PV COMBINER
 4] NEUTRAL CONDUCTORS IN EXISTING INTERIOR PANEL CAN
 NOT BE RE-BONDED TO GROUND. INSTALL INSULATED ISOLATED
 NEUTRAL BAR.